PAT TESTING CERTIFICATE
Portable Appliance Testing Documentation
BS 7671:2018 | IET Code of Practice for In-service Inspection & Testing
Certificate Incomplete
Complete all required fields below to generate a professional PAT testing certificate. Missing fields will result in an incomplete certificate.
12 required field(s) remaining
🔌 PAT Testing Standards Reference
BS 7671:2018
Requirements for Electrical Installations - IET Wiring Regulations
IET Code of Practice
In-service Inspection and Testing of Electrical Equipment
PUWER 1998
Provision and Use of Work Equipment Regulations
1
CLIENT DETAILS
2
TESTING SCHEDULE
Testing Frequency Requirements
PAT testing frequency depends on appliance type, environment, and risk assessment. Follow IET Code of Practice guidelines.
Appliance Classification & Testing Frequency
Class I (Earthed)
12 months (Office)
Class II (Double Insulated)
24 months (Office)
Class III (Safety Extra Low Voltage)
48 months (Office)
Extension Leads
12 months
3
PAT TESTING STANDARDS
Test Type | Class I Limit | Class II Limit | Extension Lead Limit | Test Voltage |
---|---|---|---|---|
Earth Continuity | ≤ 0.1Ω | N/A | ≤ 0.1Ω | 200mA DC |
Insulation Resistance | ≥ 1MΩ | ≥ 2MΩ | ≥ 1MΩ | 500V DC |
Earth Leakage | ≤ 0.75mA | ≤ 0.25mA | ≤ 0.75mA | 1.1 x Rated Voltage |
Touch Current | ≤ 0.75mA | ≤ 0.25mA | ≤ 0.75mA | 1.1 x Rated Voltage |
4
APPLIANCE TESTING
Appliance ID | Description | Class | Location | Earth Continuity (Ω) | Insulation (MΩ) | Earth Leakage (mA) | Result | Actions |
---|---|---|---|---|---|---|---|---|